Find Transfer Switches By: | Thompson Technology TS 870 Series Bypass / Isolation Automatic Transfer SwitchTS 870 Bypass / Isolation|Automatic|3 or 4 Pole|100 - 1200 AMPSPart #:thompson-870-ts-bypass-isolation-automatic-transfer-switch The TS 870 bypass isolation switch provides the same reliable features that are available in the TS 870 automatic transfer switch.The TS 870 bypass isolation switch incorporates two basic types for bypass-isolation. Type "B" (double-sided ) isolates the transfer switch and can bypass either the utility or generator source of the load, as selected by the operator. Single-sided bypass types "D" (utility bypass) and "C" (generator bypass) can bypass only one source to the load (in accordance with CSA 282-00 - Institutional & Residential Buildings Occupancy Group Band C). Note: CSA 282-00 requires (as a minimum) a single sided bypass on the generator supply. The TS 870 series mechanisms utilize enclosed contact power switching units which provide a 100% continuous rating. The switches are mounted independently on a common frame. Need More info?
Call our experienced generator specialists : 1 800 922 5632. If you would like a Continental Generators representative to contact you please submit our customer inquiry form and we will assist you as soon as possible
Features and Benefits of the TS 870 Series Bypass / Isolation:
- Enclosed Contact Power Switching Units
fully enclosed silver alloy contacts provide high withstand rating & 100% continuous current rating.
-
Barriers between the transfer switch and bypass isolation switch reduce the chance of consequential damage if there is a failure in either the transfer switch or bypass isolation switch.
-
When isolated there is no power in the transfer switch compartment providing true isolation.
-
Not damaged if manually switched while in service since contacts have inherent spring over center design.
-
Reliable Motor-Operated Transfer Mechanism
heavy duty brushless gearmotor and operating mechanism provide mechanical interlocking and extreme long life with minimal maintenance.
-
Safe manual operation with permanently affixed handle, permits easy operation under adverse conditions.
-
All control wires and power busses are front-accessible, eliminating the cost and complexity of a drawout transfer switch.
-
Control Features
TSC 80 microprocessor based controller.
-
Isolation plug permits disconnecting control circuits from all power sources for safety and convenience.
-
Control circuitry permits complete off load testing of the transfer switch when isolated (a drawout transfer switch is not required).
-
Isolation Switch allows bypass with load interruptioon (double sided bypass only).
-
Quality Assurance
ISO 9001:2000 Registered
-
Models from 100 - 1200 Amp continuous
-
Available 3 or 4 pole
-
All models 50/60Hz rated
-
Voltage range 208-600V
-
3 phase, 3 or 4 wire systems
-
CSA C22.2 No. 178/ CSA 22.2 No. 31
Control Features:
- TSC 80 microprocessor based controller.
-
isolation plug permits disconnecting control circuits from all
power sources for safety and convenience.
-
control circuitry permits complete off load testing of the transfer
-
switch when isolated (a drawout transfer switch is not required.)
-
Isolation Switch
-
allows bypass without load interruption (double sided
bypass only).
-
Quality Assurance
- ISO 9001:2000 Registered
Product Data
-
Models from 100-1200 Amp continuous
-
Available 3 or 4 pole
- All models 50/60Hz rated
- Voltage range 208-600V
- 3 phase, 3 or 4 wire systems
-
Safety Standards
-
CSA C22.2 No. 178/CSA C22.2 No. 31
-
(in accordance with CSA 282-00 - Institutional & Residential
-
Buildings Occupancy Group B and C).
Telecom, Agriculture,Municipal,Commercial /Retail, Light Industrial |
Featured ProductRobin Subaru RGD5000H Portable Generator - Robin Subaru RGD5000H Portable Generator - great for emergency generator use. click here for more info
|