Cummins Onan OTEC PowerCommand Automatic Transfer Switch Series: 40 - 100 Amps, open or delayed transition

OTEC|Automatic|3 and 4 Pole|40 - 1000 AMPS

Part #:cummins-otec-automatic-transfer-switch

Call Us
for Price
1-800-922-5632

  View Spec Sheet

OTEC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets. They are suitable for use in emergency, legally required, and optional standby applications. The switches monitor both power sources, signal generator set startup, automatically transfer power, and return the load to the primary power source once a stable utility is available.

Need More info?

Call our experienced generator specialists : 1 800 922 5632. If you would like a Continental Generators representative to contact you please submit our customer inquiry form and we will assist you as soon as possible

  • PowerCommandŽ control
  • A standard, fully featured microprocessor-based control.
  • Software-enabled features, settings, and adjustments are available for ease of setup and accuracy.
  • Advanced transfer switch mechanism
  • Unique bidirectional linear actuator provides virtually friction-free, constant force, straight-line transfer switch action during automatic operation.
  • Manual operation
  • Manual operating handles, shielded termination, and over-center type contact mechanisms allow effective, manual operation, under deenergized conditions.
  • Positive interlocking
  • Mechanical and electrical interlocking prevent source-to-source connection through the power or control wiring.
  • Main contacts
  • Heavy-duty silver alloy contacts with separate arcing surfaces and multi-leaf arc chutes are rated for total system transfer including overload interruption.
  • Easy service/access
  • Plug connections, doormounted controls, ample access space, and compatible terminal markings.
  • The control is field programmable.
  • Product lines, accessories and services
  • Cummins Power Generation offers a wide range of accessories and services to suit your requirements.
  • Warranty and service
  • Backed by a comprehensive warranty and worldwide distributor network.
    Specifications
  • Voltage rating Transfer switches rated from 40 A through 1000 A are rated up to 600 VAC, 50 or 60 Hz.
  • Arc interruption Multiple leaf arc chutes cool and quench the arcs.
  • Barriers prevent interphase flashover.
  • Neutral bar A full current-rated neutral bar with lugs is standard on enclosed 3-pole transfer switches.
  • Auxiliary contacts
  • Two contacts (one for each source) are provided for customer use.
  • Wired to terminal block for easy access.
  • Rated at 10A continuous and 250 VAC maximum.
  • Operating temperature -22 oF (-30 oC) to 140 oF (60 oC)
  • Storage temperature -40 °F (-40 °C) to 140 °F (60 °C)
  • Humidity Up to 95% relative, non-condensing
  • Altitude Up to 10,000 ft (3,000 m) without derating
  • Total transfer time (sourceto- source) Will not exceed 6 cycles at 60 Hz with normal voltage applied to the actuator and without delayed transition enabled.
  • Transfer switches are equipped with permanently attached operating handles and quick-break, quickmake contact mechanisms suitable for manual operation under de-energized conditions.