Find Industrial & Commercial Standby Generators By: | Cummins 50 KW Diesel GeneratorDGHE||Diesel|50kwPart #:DGHE Diesel powered generator sets remain the number–one choice for standby and emergency power systems, worldwide. Able to start and assume load in less than 10 seconds, and rated load in a single step, Cummins diesel generator sets are the epitome of rugged dependability and reliable mechanical and electrical performance. Diesel generators are also well suited to utility peaking plants, Distributed Generation (DG) facilities, peak shaving (or peak lopping), and power management at large commercial or industrial sites.
Need More info?
Call our experienced generator specialists : 1 800 922 5632. If you would like a Continental Generators representative to contact you please submit our customer inquiry form and we will assist you as soon as possible
- Cummins® heavy-duty engine - Rugged 4-cycle,
industrial diesel delivers reliable power, low emissions
and fast response to load changes.
-
Alternator - Several alternator sizes offer selectable
motor starting capability with low reactance 2/3 pitch
windings, low waveform distortion with non-linear loads
and fault clearing short-circuit capability.
-
Control system - The PowerCommand® 1301 electronic
control is standard equipment and provides total genset
system integration including automatic remote
starting/stopping, precise frequency and voltage
regulation, alarm and status message display, output
metering, auto-shutdown at fault detection and NFPA 110
Level 1 compliance.
- The optional PowerCommand 2100
control is UL 508 Listed and provides AmpSentry™
protection.
-
Cooling system - Standard integral set-mounted
radiator system, designed and tested for rated ambient
temperatures, simplifies facility design requirements for
rejected heat.
-
Enclosures - Optional weather protective and sound
attenuated enclosures are available.
-
Fuel tanks - Dual wall sub-base fuel tanks and in-skid
day tanks are also offered.
-
NFPA - The genset accepts full rated load in a single step
in accordance with NFPA 110 for Level 1 systems.
-
Warranty and service - Backed by a comprehensive
warranty and worldwide distributor network.
View/Download Spec Sheet
- Design Turbocharged
-
Bore 95.0 mm (3.74 in)
-
Stroke 115.1 mm (4.53 in)
-
Displacement 3.3 L (199.0 in3)
-
Cylinder block Cast iron, in-line, 4 cylinder
-
Battery capacity 550 amps minimum at ambient temperature of 0 °C (32 °F)
-
Battery charging alternator 35 amps
-
Starting voltage 12 volt, negative ground
-
Fuel system Direct injection: number 2 diesel fuel
-
Fuel filter
-
Single element, 10 micron filtration, spin-on fuel filter with water
separator
-
Air cleaner type Dry replaceable element
-
Lube oil filter type(s) One spin-on, full flow filter
-
Standard cooling system 40 °C (104 °F) ambient radiator
Industrial Use |