CAT 20 KW LP/Propane Standby Power Generator

G20UH3|Single Phase|LP/Propane, Natural Gas|20 KW

Part #:

Call for Pricing
and nearest dealer location.

freight not included click here for shipping info

  View Spec Sheet

This complete power generation system is designed and built at ISO 9001 certified facilities and factory tested to design specifications at full load conditions to ensure maximum reliability and top performance.

Need More info?

Call our experienced generator specialists : 1 800 922 5632. If you would like a Continental Generators representative to contact you please submit our customer inquiry form and we will assist you as soon as possible

    Engine
  • Governor, Woodward electronic
  • Electrical system, 12 VDC
  • Cartridge type filters
  • Natural gas fuel system, LP gas options available
  • Gas shutoff valve, solenoid operated
  • Gas pressure regulator
  • Low oil pressure shutdown
    Generator
  • Insulation system, class H
  • Drip proof generator air intake (NEMA 2, IP23)
  • Electrical design in accordance with BS5000 Part 99, IEC60034-1, EN61000-6, NEMA MG-1.33, UTE51100 Automatic Voltage Regulator
  • Voltage within ± 0.5% 3 Phase and 1.0% Single Phase at steady state from no load to full load
  • Provides fast recovery from transient load changes Cooling System
  • Radiator and cooling fan complete with protective guards
  • Standard ambient temperatures up to 110° F (43° C)
  • High coolant temperature shutdown
  • Low coolant level shutdown
  • Low coolant temperature alarm
  • Mounting Arrangement
  • Heavy-duty fabricated steel base with lifting points
  • Anti-vibration pads to ensure vibration isolation
  • Battery, rack, and cables
  • Coolant and lube oil drains piped to edge of base
  • Complete OSHA guarding
  • Stub-up pipe ready for connection to silencer pipework
  • Weather protective enclosures are available
  • Fuel line terminated at base with NPT connections
  • Circuit Breaker
  • 3-pole with solid neutral, UL/CSA listed
  • NEMA 1 steel enclosure, vibration isolated
  • Electrical stub-up area directly below circuit breaker
  • EMCP3.1 control panel
  • Vibration isolated NEMA 1 enclosure with hinged access door
  • Engine and generator instrumentation
  • Volts adjust potentiometer
  • Safety shutdown and alarm indicators
  • Audible alarm for all faults
  • Volt-free contact for common alarm
  • AC/DC wiring with multi-pin connectors for system flexibility
  • All electroplated hardware
  • Anticorrosive protection prior to painting
  • High gloss polyurethane paint for durability and scuff resistance
  • Operation and maintenance manuals provided
  • Wiring diagrams included
  • Warranty

  View/Download Spec Sheet

  • Voltage Regulation................... ±0.5% 3 Phase and ±1.0%
  • 1 Phase at steady state from no load to full load Frequency............................±0.25% for constant load, no load to full load
  • Waveform Distortion.........................THD less than 4%,
  • Radio Interference...................................EN61000-6
  • Telephone Influence Factor..............................TIF <50 per NEMA MG 1-32.11
  • Telephone Harmonic Factor.......................... THF <2% Stator................................................ 2/3 pitch
  • Type......................................Brushless, self excited, 12 reconnectable leads
  • Insulation......................... Class H per NEMA MG1-1.66
  • Temperature Rise.......................... Within Class H limits
  • Overspeed Capability.................................... 125%
  • Available Voltages......................... 1-Phase — 240/120, 220/110 3-Phase — 480/277, 240/120, 208/120
  • Ratings....................... At 77° F (25° C), 500 ft. (152.4 m), 60% humidity, 0.8 pf (3-Phase), 1.0 pf (1-Phase)
  • ENGINE Manufacturer.......................................... HM Ltd.
  • Model..................................................... 1.8L
  • Type ................................................... 4-Cycle
  • Aspiration.............................................. Natural
  • Cylinder Configuration................................ In-line 4
  • Displacement — cu in (L) ........................... 109.8 (1.8)
  • Bore — in (mm) ...................................... 3.3 (84.0)
  • Stroke — in (mm) .................................... 3.2 (82.0)
  • Compression Ratio ....................................... 8.5: Governor
  • Type.............................................. Electronic
  • Class............................................ISO 8528 G2
  • Piston Speed — ft/sec (m/sec)........................ 16.1 (4.9)
  • Air Cleaner Type..........................Replaceable Element, LP/Gas
  • Engine Speed — rpm..................................... 3600
  • Max Power at Rated rpm — hp (kW)
  • Standby........................................... 26.0 (19.5) BMEP — psi (kPa)
  • Standby........................................ 103.7 (715.0)Natural Gas
  • Engine Speed — rpm..................................... 3600 Max Power at Rated rpm — hp (kW)
  • Standby........................................... 25.0 (19.0)BMEP — psi (kPa)
  • Standby........................................ 121.3 (836.0)
Industrial Use.

Featured Product

Robin Subaru RGD5000H Portable Generator - Robin Subaru RGD5000H Portable Generator - great for emergency generator use.

click here for more info