Find Industrial & Commercial Standby Generators By: | CAT 150 KW Natural Gas Standby Power GeneratorG150GI|Three Phase|Natural Gas|150 KWPart #:cat-150-kw-natural-gas-standby-industrial-generator The CAT 150 KW Natural Gas Standby Industrial Generation System is designed and built at ISO 9001 certified facilities and factory tested to design specifications at full load conditions to ensure maximum reliability and top performance. Need More info?
Call our experienced generator specialists : 1 800 922 5632. If you would like a Continental Generators representative to contact you please submit our customer inquiry form and we will assist you as soon as possible
Generating Set
- Complete system designed and built at ISO 9001
certified facilities
-
Factory tested to design specifications at full load
conditions
Engine
- Governor, Isochronous electronic
-
Electrical system, 12 VDC
-
Cartridge type filters
-
Battery, rack, and cables
-
Coolant and lube oil drains piped to edge of base
Generator
-
Insulation system, class H
-
Drip proof generator air intake (NEMA 2, IP23)
-
Electrical design in accordance with BS5000 Part 99,
IEC60034-1, EN61000-6, NEMA MG-1.33
Automatic Voltage Regulator
- Voltage within ± 0.5% 3 Phase at steady state from no
load to full load
-
Provides fast recovery from transient load changes
Cooling System
-
Radiator and cooling fan complete with protective
guards
-
Standard ambient temperatures up to 131° F (55° C)
Mounting Arrangement
-
Heavy-duty fabricated steel base with lifting points
-
Anti-vibration pads to ensure vibration isolation
-
Complete OSHA guarding
-
Stub-up pipe ready for connection to silencer
pipework
-
Sound attenuated enclosures are available
-
Flexible fuel lines to base with NPT connections
View/Download Spec Sheet
- Voltage Regulation.. . . . ±0.5% 3 Phase and 1.0% Single
Phase at steady state from no load to full load
-
Frequency.. . . . . . . . . . . . . . . . . . ±0.25% for constant load
-
Waveform Distortion.. . . . . . . . . . . . . . . . THD less than 4%,
no load to full load
-
Radio Interference. . . . . . . . . Compliance with EN61000-6
-
Telephone Influence Factor.. . . . . . . . . . . . . . . . . . . . TIF <50
per NEMA MG 1-32.11
-
Telephone Harmonic Factor.. . . . . . . . . . . . . . . . . . THF <2%
-
Stator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2/3 pitch
-
Type.. . . . . . . . . . . . . . . . . . . . . . . . . . . Brushless, self excited,
12 reconnectable leads
-
Insulation.. . . . . . . . . . . . . . . . Class H per NEMA MG1-1.66
-
Temperature Rise.. . . . . . . . . . . . . . . . Within Class H limits
-
Overspeed Capability.. . . . . . . . . . . . . . . . . . . . . . . . . . . 125%
-
Available Voltages. . . . . . . . . . 1-Phase — 120/240, 110/220
3-Phase — 277/480,
120/240, 120/208
-
Deration.. . . . . . . . . . . . . . . . . . . . . . . Please consult factory
for available outputs
-
Ratings.. . . . . . . . . . . . . At 77° F (25° C), 500 ft. (152.4 m),
60% humidity, 1.0 pf (1-Phase)
0.8 pf (3-Phase)
-
ENGINE
Manufacturer.. . . . . . . . . . . . . . . . . . . . . . . . Ford Motor Co.
-
Model.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WSG1068 Turbo
-
Type .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Cycle
-
Aspiration.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Turbocharged
Cylinder
-
Configuration.. . . . . . . . . . . . . . . . . . . . . . . . . . . V10
-
Displacement — cu in (L) .. . . . . . . . . . . . . . . . . 415.0 (6.8)
-
Bore — in (mm) .. . . . . . . . . . . . . . . . . . . . . . . . . . . 3.6 (90.2)
-
Stroke — in (mm) .. . . . . . . . . . . . . . . . . . . . . . . . 4.2 (105.8)
-
Compression Ratio .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.0:1
-
Governor
Type.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electronic
-
Class.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
-
Piston Speed — ft/sec (m/sec).. . . . . . . . . . . . . . 20.7 (6.3)
-
Air Cleaner Type. . . . . . . . . . . . . . . . . Replaceable Element
-
Natural Gas
Engine Speed — rpm.. . . . . . . . . . . . . . . . . . . . . . . . . . . 1800
-
Max Power at Rated rpm — hp (kW)
Standby.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163.0 (121.4)
-
BMEP — psi (kPa)
Standby.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208.4 (1437.0)
Industrial Use. |
Featured ProductRobin Subaru RGD5000H Portable Generator - Robin Subaru RGD5000H Portable Generator - great for emergency generator use. click here for more info
|